• Robert Dansertlaan 250, 1702 Groot-Bijgaarden, Belgium

Porseleinen onderstationisolatoren voor buiten

Porseleinen onderstationisolatoren voor buiten

Porseleinen onderstationisolatoren voor buiten
Download

Ceramic / porcelain material

Ceramic groupCeramic groupCeramic groupCeramic group
Sub-GroupC-110C-120C-130C-221
Silicious
Porcelain
Aluminous porcelain
Standard strength
Aluminous porcelain
High strength
Steatite low/loss
angle
PropertiesPropertiesPropertiesSymbolsUnitsAL2O3
<30%
AL2O3
30-50%
AL2O3
>50%
Apparent prosity (open)max.max.PaVolume %0.00.00.00.0
Bulk densitymin.min.δag/cm32,22,32,52,7
Flexural strengthmin.unglazedRfN/mm25090140140
min.glazedRfN/mm260110160-
Modulus of elasticityminEGPa6070100100
Mean coefficient linear expansionα 20-100°C10-6K-13-63-64-76-8
α 20-300°C10-6K-13-63-65-77-9
α 20-600°C10-6K-14-75-75-78-9
Specific heat capacity20°-100°CcpJ/kgK750÷900750÷900750÷900790÷920
Thermal conductivity20°-100°CλW/mK1÷2,51,2÷2,61,5÷4,02,3÷2,8
Resistance to thermal shockmin.ΔtK150150150100
Electric strengthmin.EdkV/mm20202020
Withstand voltagemin.UkV30303030
Relative permittivity48÷62 Hzεr6÷76÷76÷7,56
Dissipational 20°Cmax.48÷62 Hztanδ10-32525301,5
max.1 kHztanδ10-3----
max.1 MHztanδ10-31212151,2
Volume resistivity in terms of temperaturemin.20°CρvΩcm1013101310131012
min.200°CρvΩcm1081081081011
min.600°CρvΩcm104104104107
Temperature corresponding to a volume resistivitymin.100 MΩcmtK100°C200200200500
min.1 MΩcmtK1°C350350350800
For post insulators, hot-dip galvanized cast iron flanges assembled or with :
Sulphur cement = excellent mechanical performances and max use temperature 90°C - Reduced assembly time
Portland cement = max use temperature 200°C - Drying time in mould is longer

Porseleinen isolator met vaste kern voor buiten 12 kV

Outdoor solid-core post insulator 12 kV

TYPE123H ± 1CrPol.NN2ØDd1tap d1d2tap d2Weight
kVkVkVmmmmClassNNmmmmmmkg
C4-75122875215192140001000140764xM12764xM125,2
C4-75122875215240240001000136764xM12764xM12
C4-75122875215300340001000150764xM12764xM12
C8-75122875215192180001000140764xM12764xM125,2
C8-75122875215240280001000140764xM12764xM125,2
C8-75122875215300380001000185764xM12764xM125,2
C12,5-751228752151921125001500144764xM12764xM12
C12,5-751228752152402125001500160764xM12764xM12
C12,5-751228752153003125001500175764xM12764xM12
1 - Rated Highest voltage for equipment (Um)
2 - Rated Power Frequency Withstand Voltage, wet (50 Hz, 1 min)
3 - Rated Lightning impulse withstand (1.2/50 μs)
Cr - Creepage distance
Pol - Polution class acc IEC60815
N - Flexion resistance
N2 - Torsion failing load N.m

Porseleinen isolator met vaste kern voor buiten 17,5 kV

Outdoor solid-core post insulator 17,5 kV

TYPE123H ± 1CrPol.NN2ØDd1tap d1d2tap d2Weight
kVkVkVmmmmClassNNmmmmmmkg
C4-9517,53895255280140001000140764xM12764xM126
C4-9517,53895255350240001000140764xM12764xM12
C4-9517,53895255437,5340001000185764xM12764xM12
C8-9517,53895255280180002000150764xM12764xM126,8
C8-9517,53895255350280002000160764xM12764xM12
C8-9517,53895255437,5380002000167764xM12764xM12
C12,5-9517,538952552801125002000150764xM12764xM1210,5
C12,5-9517,538952553502125002000165764xM12764xM12
C12,5-9517,53895255437,53125002000180764xM12764xM12
1 - Rated Highest voltage for equipment (Um)
2 - Rated Power Frequency Withstand Voltage, wet (50 Hz, 1 min)
3 - Rated Lightning impulse withstand (1.2/50 μs)
Cr - Creepage distance
Pol - Polution class acc IEC60815
N - Flexion resistance
N2 - Torsion failing load N.m

Porseleinen isolator met vaste kern voor buiten 24 kV

Outdoor solid-core post insulator 24 kV - BIL 125 kV

TYPE123H ± 1CrPol.NN2ØDd1tap d1d2tap d2Weight
kVkVkVmmmmClassNNmmmmmmkg
C4-1252450125305384140001000148764xM12764xM126,6
C4-1252450125305480240001000150764xM12764xM127,7
C4-1252450125305600340001000190764xM12764xM1210
C8-1252450125305384180002000164764xM12764xM1210,5
C8-1252450125305480280002000202764xM12764xM1212,5
C8-1252450125305600380002000174764xM12764xM12
C12,5-12524501253053841125002000170764xM12764xM1212,5
C12,5-12524501253054802125002000175764xM12764xM12
C12,5-12524501253056003125002000226764xM12764xM12
1 - Rated Highest voltage for equipment (Um)
2 - Rated Power Frequency Withstand Voltage, wet (50 Hz, 1 min)
3 - Rated Lightning impulse withstand (1.2/50 μs)
Cr - Creepage distance
Pol - Polution class acc IEC60815
N - Flexion resistance
N2 - Torsion failing load N.m

Porseleinen isolator met vaste kern voor buiten 24 kV - BIL 150 kV

Outdoor solid-core post insulator 24 kV - BIL 150kV

TYPE123H ± 1CrPol.NN2ØDd1tap d1d2tap d2Weight
kVkVkVmmmmClassNNmmmmmmkg
C4-1502450150355384140001000157764xM12764xM12
C4-1502450150355480240001000155764xM12764xM12
C4-1502450150355600340001000140764xM12764xM12
C8-1502450150355384180001500170764xM12764xM12
C8-1502450150355480280001500163764xM12764xM12
C8-1502450150355600380001500178764xM12764xM12
C12,5-15024501503553841125002500165764xM12764xM12
C12,5-15024501503554802125002500178764xM12764xM12
C12,5-15024501503556003125002500185764xM12764xM12
1 - Rated Highest voltage for equipment (Um)
2 - Rated Power Frequency Withstand Voltage, wet (50 Hz, 1 min)
3 - Rated Lightning impulse withstand (1.2/50 μs)
Cr - Creepage distance
Pol - Polution class acc IEC60815
N - Flexion resistance
N2 - Torsion failing load N.m

Porseleinen isolator met vaste kern voor buiten 36 kV - BIL 170 kV

Outdoor solid-core post insulator 36 kV - BIL 170 kV

TYPE123H ± 1CrPolNN2ØDd1tap d1d2tap d2Weight
kVkVkVmmmmClassNNmmmmmmkg
C4-1703670170445576140001200144764xM12764xM1211
C4-1703670170445720240001200190764xM12764xM1213
C4-1703670170445900340001200184764xM12764xM12
C4-17036701704451116440001200200764xM12764xM12
C6-1703670170445576160001500144764xM12764xM1212
C6-1703670170445720260001500168764xM12764xM1214
C6-1703670170445900360001500194764xM12764xM12
C6-17036701704451116460001500200764xM12764xM12
C8-1703670170445576180002000153764xM12764xM1213
C8-1703670170445720280002000173764xM12764xM1215
C8-1703670170445900380002000202764xM12764xM12
C8-17036701704451116480002000213764xM12764xM12
C10-17036701704455761100002500162764xM12764xM12
C10-17036701704457202100002500173764xM12764xM12
C10-17036701704459003100002500202764xM12764xM12
C12,5-170367017044557611250030001741274xM161274xM1617
C12,5-170367017044572021250030002201274xM161274xM1619
C12,5-170367017044590031250030002201274xM161274xM16
1 - Rated Highest voltage for equipment (Um)
2 - Rated Power Frequency Withstand Voltage, wet (50 Hz, 1 min)
3 - Rated Lightning impulse withstand (1.2/50 μs)
Cr - Creepage distance
Pol - Polution class acc IEC60815
N - Flexion resistance
N2 - Torsion failing load N.m

Porseleinen isolator met vaste kern voor buiten 36 kV - BIL 200 kV

Outdoor solid-core post insulator 36 kV - BIL 200 kV

TYPE123H ± 1CrPolNN2ØDd1tap d1d2tap d2Weight
kVkVkVmmmmClassNNmmmmmmkg
C4-2003670200475576140001200170764xM12764xM1212
C4-2003670200475720240001200166764xM12764xM1214
C4-2003670200475900340001200184764xM12764xM12
C4-20036702004751116440001200204764xM12764xM12
C6-2003670200475576160001800150764xM12764xM1213
C6-2003670200475720260001800170764xM12764xM1215
C6-2003670200475900360001800195764xM12764xM12
C6-20036702004751116460001800195764xM12764xM12
C8-2003670200475576180002000155764xM12764xM1214
C8-2003670200475720280002000177764xM12764xM1216
C8-2003670200475900380002000202764xM12764xM12
C8-20036702004751116480002000222764xM12764xM12
C10-20036702004755761100002500165764xM12764xM12
C10-20036702004757202100002500177764xM12764xM12
C10-20036702004759003100002500208764xM12764xM12
C10-200367020047511164100002500228764xM12764xM12
C12,5-200367020047557611250030001721274xM161274xM1618
C12,5-200367020047572021250030002051274xM161274xM1621
C12,5-200367020047590031250030002151274xM161274xM16
C12,5-2003670200475111641250030002351274xM161274xM16
1 - Rated Highest voltage for equipment (Um)
2 - Rated Power Frequency Withstand Voltage, wet (50 Hz, 1 min)
3 - Rated Lightning impulse withstand (1.2/50 μs)
Cr - Creepage distance
Pol - Polution class acc IEC60815
N - Flexion resistance
N2 - Torsion failing load N.m

Porseleinen isolator met vaste kern voor buiten 52 kV - BIL 250 kV

Outdoor solid-core post insulator 52 kV - BIL 250 kV

TYPE123H ± 1CrPolNN2ØDd1tap d1d2tap d2Weight
kVkVkVmmmmClassNNmmmmmmkg
C4-2505295250560832140001800142764xM12764xM1214
C4-25052952505601040240001800190764xM12764xM1216
C4-25052952505601300340001800220764xM12764xM12
C4-25052952505601612440001800205764xM12764xM12
C6-2505295250560832160002000152764xM12764xM1216
C6-25052952505601040260002000165764xM12764xM1218
C6-25052952505601300360002000187764xM12764xM12
C6-25052952505601612460002000215764xM12764xM12
C8-25052952505608501800025001661274xM161274xM1621
C8-250529525056010402800025001941274xM161274xM1622
C8-250529525056013003800025002121274xM161274xM16
C8-250529525056016124800025002241274xM161274xM16
C10-250529525056085011000030001741274xM161274xM16
C10-2505295250560104021000030001991274xM161274xM16
C10-2505295250560130031000030002211274xM161274xM16
C12,5-250529525056083211250040001801274xM161274xM1623
C12,5-25052952505601040212500400011901274xM161274xM1627
C12,5-2505295250560130031250040002151274xM161274xM16
1 - Rated Highest voltage for equipment (Um)
2 - Rated Power Frequency Withstand Voltage, wet (50 Hz, 1 min)
3 - Rated Lightning impulse withstand (1.2/50 μs)
Cr - Creepage distance
Pol - Polution class acc IEC60815
N - Flexion resistance
N2 - Torsion failing load N.m

Porseleinen isolator met vaste kern voor buiten 72,5 kV - BIL 325 kV

Outdoor solid-core post insulator 72,5 kV - BIL 325 kV

TYPE123H ± 1CrPolNN2ØDd1tap d1d2tap d2Weight
kVkVkVmmmmClassNNmmmmmmkg
C4-32572,514032577011601400020001651274xM161274xM1624
C4-32572,514032577014502400020001881274xM161274xM1626
C4-32572,51403257701812,53400020002071274xM161274xM1627
C4-32572,51403257702247,54400020002301274xM161274xM16
C6-32572,514032577011601600025001661274xM161274xM1624
C6-32572,514032577014502600025001661274xM161274xM1626
C6-32572,51403257701812,53600025001801274xM161274xM1627
C6-32572,51403257702247,54600025002321274xM161274xM16
C8-32572,514032577011601800030001751274xM161274xM1629
C8-32572,514032577014502800030001811274xM161274xM1631
C8-32572,51403257701812,53800030001851274xM161274xM1632
C8-32572,51403257702247,54800030002301274xM161274xM16
C10-32572,5140325770116011000040001841274xM161274xM16
C10-32572,5140325770145021000040002051274xM161274xM16
C10-32572,51403257701812,531000040002231274xM161274xM16
C10-32572,51403257702247,541000040002351274xM161274xM16
C12,5-32572,5140325770116011250040002001274xM161274xM1633
C12,5-32572,5140325770145021250040002101274xM161274xM1634
C12,5-32572,51403257701812,531250040002371274xM161274xM1635
C12,5-32572,51403257702247,541250040002551274xM161274xM16
C16-32572,5140325770116011600050002051274xM161274xØ18
C16-32572,5140325770145021600050002301274xM161274xØ18
C16-32572,51403257701812,531600050002451274xM161274xØ18
C16-32572,51403257702247,541600050002681274xM161274xØ18
1 - Rated Highest voltage for equipment (Um)
2 - Rated Power Frequency Withstand Voltage, wet (50 Hz, 1 min)
3 - Rated Lightning impulse withstand (1.2/50 μs)
Cr - Creepage distance
Pol - Polution class acc IEC60815
N - Flexion resistance
N2 - Torsion failing load N.m

Porseleinen isolator met vaste kern voor buiten 100kV - BIL 450kV

Outdoor solid-core post insulator 100 kV - BIL 450 kV

TYPE123H ± 1CrPolNN2ØDd1tap d1d2tap d2Weight
kVkVkVmmmmClassNNmmmmmmkg
C4-450100185450102016001400025001781274xM161784xØ1834
C4-450100185450102020002400025001801274xM161784xØ1839
C4-450100185450102025003400025002071274xM161784xØ1843
C4-450100185450102031004400025002441274xM161784xØ18
C6-450100185450102016001600035001901274xM161784xØ1840
C6-450100185450102020002600035002061274xM161784xØ1843
C6-450100185450102025003600035002081274xM161784xØ1846
C6-450100185450102031004600035002421274xM161784xØ18
C8-450100185450102016001800040001971274xM162004xØ1846
C8-450100185450102020002800040002031274xM162004xØ1851
C8-450100185450102025003800040002171274xM162004xØ1856
C8-450100185450102031004800040002321274xM162004xØ18
C10-4501001854501020160011000040001961274xM162254xØ18
C10-4501001854501020200021000040002251274xM162254xØ18
C10-4501001854501020250031000040002331274xM162254xØ18
C10-4501001854501020310041000040002601274xM162254xØ18
C12,5-4501001854501020160011250060002051274xM162254xØ1858
C12,5-4501001854501020200021250060002261274xM162254xØ1862
C12,5-4501001854501020250031250060002501274xM162254xØ1867
C12,5-4501001854501020310041250060002701274xM162254xØ18
C16-4501001854501020160011600060002201274xM162258xØ18
C16-4501001854501020200021600060002501274xM162258xØ18
C16-4501001854501020250031600060002551274xM162258xØ18
C16-4501001854501020310041600060002851274xM162258xØ18
C20-4501001854501020160012000060002301274xM162548xØ18
C20-4501001854501020200022000060002431274xM162548xØ18
C20-4501001854501020250032000060002751274xM162548xØ18
C20-4501001854501020310042000060002931274xM162548xØ18
1 - Rated Highest voltage for equipment (Um)
2 - Rated Power Frequency Withstand Voltage, wet (50 Hz, 1 min)
3 - Rated Lightning impulse withstand (1.2/50 μs)
Cr - Creepage distance
Pol - Polution class acc IEC60815
N - Flexion resistance
N2 - Torsion failing load N.m

Porseleinen isolator met vaste kern voor buiten 123kV - BIL 550kV

Outdoor solid-core post insulator 123 kV - BIL 550 kV

TYPE123H ± 1CrPolNN2ØDd1tap d1d2tap d2Weight
kVkVkVmmmmClassNNmmmmmmkg
C4-550123230550122019681400030001851274xM161784xØ18
C4-550123230550122024602400030002081274xM161784xØ18
C4-550123230550122030753400030002171274xM161784xØ18
C4-550123230550122038134400030002501274xM161784xØ18
C6-550123230550122019681600040001851274xM162004xØ18
C6-550123230550122024602600040002221274xM162004xØ18
C6-550123230550122030753600040002321274xM162004xØ18
C6-550123230550122038134600040002651274xM162004xØ18
C8-550123230550122019681800040001961274xM162004xØ18
C8-550123230550122024602800040002431274xM162004xØ18
C8-550123230550122030753800040002451274xM162004xØ18
C8-550123230550122038134800040002491274xM162004xØ18
C10-5501232305501220196811000040002081274xM162254xØ18
C10-5501232305501220246021000040002431274xM162254xØ18
C10-5501232305501220307531000040002521274xM162254xØ18
C10-5501232305501220381341000040002701274xM162254xØ18
C12,5-5501232305501220196811250060002211274xM162548xØ18
C12,5-5501232305501220246021250060002521274xM162548xØ18
C12,5-5501232305501220307531250060002661274xM162548xØ18
C12,5-5501232305501220381341250060002781274xM162548xØ18
C16-5501232305501220196811600060002461274xM162548xØ18
C16-5501232305501220246021600060002761274xM162548xØ18
C16-5501232305501220307531600060002901274xM162548xØ18
C16-5501232305501220381341600060002951274xM162548xØ18
C20-5501232305501220196812000060002471274xM162758xØ18
C20-5501232305501220246022000060002721274xM162758xØ18
C20-5501232305501220307532000060002911274xM162758xØ18
C20-5501232305501220381342000060003091274xM162758xØ18
1 - Rated Highest voltage for equipment (Um)
2 - Rated Power Frequency Withstand Voltage, wet (50 Hz, 1 min)
3 - Rated Lightning impulse withstand (1.2/50 μs)
Cr - Creepage distance
Pol - Polution class acc IEC60815
N - Flexion resistance
N2 - Torsion failing load N.m

Porseleinen isolator met vaste kern voor buiten 145kV - BIL 650kV

Outdoor solid-core post insulator 145 kV - BIL 650 kV

TYPE123H ± 2,5CrPolNN2ØDd1tap d1d2tap d2Weight
kVkVkVmmmmClassNNmmmmmmkg
C4-650145275650150023201400030001851274xM162004xØ18
C4-650145275650150029002400030002101274xM162004xØ18
C4-650145275650150036253400030002201274xM162004xØ18
C4-650145275650150044954400030002601274xM162004xØ18
C6-650145275650150023201600030001881274xM162004xØ18
C6-650145275650150029002600030001881274xM162004xØ18
C6-650145275650150036253600030002401274xM162004xØ18
C6-650145275650150044954600030002531274xM162004xØ18
C8-650145275650150023201800040002101274xM162254xØ18
C8-650145275650150029002800040002381274xM162254xØ18
C8-650145275650150036253800040002521274xM162254xØ18
C8-650145275650150044954800040002521274xM162254xØ18
C10-6501452756501500232011000040002151274xM162548xØ18
C10-6501452756501500290021000040002511274xM162548xØ18
C10-6501452756501500362531000040002651274xM162548xØ18
C10-6501452756501500449541000040002671274xM162548xØ18
C12,5-6501452756501500232011250060002301274xM162548xØ18
C12,5-6501452756501500290021250060002511274xM162548xØ18
C12,5-6501452756501500362531250060002701274xM162548xØ18
C12,5-6501452756501500449541250060002751274xM162548xØ18
C16-6501452756501500232011600060002462254xØ182758xØ18
C16-6501452756501500290021600060002762254xØ182758xØ18
C16-6501452756501500362531600060002902254xØ182758xØ18
C16-6501452756501500449541600060002952254xØ182758xØ18
C20-6501452756501500232012000060002562254xØ183008xØ18
C20-6501452756501500290022000060002862254xØ183008xØ18
C20-6501452756501500362532000060003002254xØ183008xØ18
C20-6501452756501500449542000060003052254xØ183008xØ18
1 - Rated Highest voltage for equipment (Um)
2 - Rated Power Frequency Withstand Voltage, wet (50 Hz, 1 min)
3 - Rated Lightning impulse withstand (1.2/50 μs)
Cr - Creepage distance
Pol - Polution class acc IEC60815
N - Flexion resistance
N2 - Torsion failing load N.m

Porseleinen isolator met vaste kern voor buiten 170kV - BIL 750kV

Outdoor solid-core post insulator 170 kV - BIL 750 kV

TYPE123H ± 2,5CrPolNN2ØDd1tap d1d2tap d2Weight
kVkVkVmmmmClassNNmmmmmmkg
C4-750170325750170027201400030001901274xM162004xØ18
C4-750170325750170034002400030002161274xM162004xØ18
C4-750170325750170042503400030002421274xM162004xØ18
C4-750170325750170052704400030002561274xM162004xØ18
C6-750170325750170027201600030002001274xM162254xØ18
C6-750170325750170034002600030002351274xM162254xØ18
C6-750170325750170042503600030002501274xM162254xØ18
C6-750170325750170052704600030002501274xM162254xØ18
C8-750170325750170027201800040002111274xM162254xØ18
C8-750170325750170034002800040002331274xM162254xØ18
C8-750170325750170042503800040002461274xM162254xØ18
C8-750170325750170052704800040002611274xM162254xØ18
C10-7501703257501700272011000040002231274xM162548xØ18
C10-7501703257501700340021000040002531274xM162548xØ18
C10-7501703257501700425031000040002571274xM162548xØ18
C10-7501703257501700527041000040002811274xM162548xØ18
C12,5-7501703257501700272011250060002501274xM162548xØ18
C12,5-7501703257501700340021250060002531274xM162548xØ18
C12,5-7501703257501700425031250060002931274xM162548xØ18
C12,5-7501703257501700527041250060002991274xM162548xØ18
C16-7501703257501700272011600060002652254xØ182758xØ18
C16-7501703257501700340021600060002942254xØ182758xØ18
C16-7501703257501700425031600060003082254xØ182758xØ18
C16-7501703257501700527041600060003142254xØ182758xØ18
C20-7501703257501700272012000060002652254xØ183008xØ18
C20-7501703257501700340022000060002952254xØ183008xØ18
C20-7501703257501700425032000060003082254xØ183008xØ18
C20-7501703257501700527042000060003152254xØ183008xØ18
1 - Rated Highest voltage for equipment (Um)
2 - Rated Power Frequency Withstand Voltage, wet (50 Hz, 1 min)
3 - Rated Lightning impulse withstand (1.2/50 μs)
Cr - Creepage distance
Pol - Polution class acc IEC60815
N - Flexion resistance
N2 - Torsion failing load N.m

Porseleinen isolator met vaste kern voor buiten 245 kV - BIL 950kV

Outdoor solid-core post insulator 245kV - BIL 950 kV

TYPE1234H ± 3,5CrPolNN2ØDd1tap d1d2tap d2Weight
kVkVkVkVmmmmClassNNmmmmmmkg
C4-950245395950750210039201400030001961274xM162004xØ18
C4-950245395950750210049002400030002261274xM162004xØ18
C4-950245395950750210061253400030002601274xM162004xØ18
C6-950245395950750210039201600030002111274xM162254xØ18
C6-950245395950750210049002600030002251274xM162254xØ18
C6-950245395950750210061253600030002751274xM162254xØ18
C8-950245395950750210039201800040002231274xM162548xØ18
C8-950245395950750210049002800040002501274xM162548xØ18
C8-950245395950750210061253800040002721274xM162548xØ18
C10-9502453959507502100392011000040002311274xM162548xØ18
C10-9502453959507502100490021000040002611274xM162548xØ18
C10-9502453959507502100612531000040002951274xM162548xØ18
C12,5-9502453959507502100392011250060002481274xM162758xØ18
C12,5-9502453959507502100490021250060002761274xM162758xØ18
C12,5-9502453959507502100612531250060003101274xM162758xØ18
1 - Rated Highest voltage for equipment (Um)
2 - Rated Power Frequency Withstand Voltage, wet (50 Hz, 1 min)
3 - Rated Lightning impulse withstand (1.2/50 μs)
Cr - Creepage distance
Pol - Polution class acc IEC60815
N - Flexion resistance
N2 - Torsion failing load N.m

Porseleinen isolator met vaste kern voor buiten 245 kV - BIL 950kV

Outdoor solid-core post insulator 245kV - BIL 1050 kV

TYPE1234H ± 3,5CrPolNN2ØDd1tap d1d2tap d2Weight
kVkVkVkVmmmmClassNNmmmmmmkg
C4-10502454601050750230039201400030002011274xM162004xØ18
C4-10502454601050750230049002400030002351274xM162004xØ18
C4-10502454601050750230061253400030002601274xM162004xØ18
C4-10502454601050750230075954400030002901274xM162004xØ18
C6-10502454601050750230039201600030002161274xM162254xØ18
C6-10502454601050750230049002600030002801274xM162254xØ18
C6-10502454601050750230061253600030002601274xM162254xØ18
C6-10502454601050750230075954600030002851274xM162254xØ18
C8-10502454601050750230039201800040002261274xM162548xØ18
C8-10502454601050750230049002800040002471274xM162548xØ18
C8-10502454601050750230061253800040002721274xM162548xØ18
C8-10502454601050750230075954800040002951274xM162548xØ18
C10-105024546010507502300392011000040002281274xM162758xØ18
C10-105024546010507502300490021000040002711274xM162758xØ18
C10-105024546010507502300612531000040003041274xM162758xØ18
C10-105024546010507502300759541000040003111274xM162758xØ18
C12,5-105024546010507502300392011250060002501274xM162758xØ18
C12,5-105024546010507502300490021250060002831274xM162758xØ18
C12,5-105024546010507502300612531250060003111274xM162758xØ18
C12,5-105024546010507502300759541250060003181274xM162758xØ18
C16-105024546010507502300392011600060002672254xØ183008xØ18
C16-105024546010507502300490021600060002972254xØ183008xØ18
C16-105024546010507502300612531600060003132254xØ183008xØ18
C16-105024546010507502300759541600060003362254xØ183008xØ18
1 - Rated Highest voltage for equipment (Um)
2 - Rated Power Frequency Withstand Voltage, wet (50 Hz, 1 min)
3 - Rated Lightning impulse withstand (1.2/50 μs)
Cr - Creepage distance
Pol - Polution class acc IEC60815
N - Flexion resistance
N2 - Torsion failing load N.m