• Robert Dansertlaan 250, 1702 Groot-Bijgaarden, Belgium

Ceramic - Transformator bushings

Transformator bushings

Ceramic transformator bushing 1 kV acc to DIN42530

DIN42530 Transformer bushing - 1kV - 250A or 630A

Rated Voltage : 1 kV
Max Voltage : 1.1 kV
Lightning Impulse : 20 kV
Power frequency withstnd (Dry&Wet) : 10 kV
TypeRated currentCreepage distancea maxb maxs +/-0,3d1d3d4d5Weight
1/250250A55 mm1386825M122860501,7 kg
1/630630A70 mm1788237M204585703,7 kg

Ceramic transformator bushing 1 kV acc to DIN42530

DIN42530 Transformer bushing - 1kV - 1000A - 2000A - 3150A

Rated Voltage : 1 kV
Max Voltage : 1.1 kV
Lightning Impulse : 20 kV
Power frequency withstnd (Dry&Wet) : 10 kV
TypeRated currentCreepage distancea maxb maxcd1d3d4d5x1x2b1b2l2Weight
1/10001250A75 mm2596070M30x2561109017261726606,1
1/20002000A75 mm34070100M42x37012510420402510010011,5
1/31503150A75 mm34270110M48x39015012520403012012014

Ceramic transformator bushing 1 kV acc to DIN42530

Ceramic transformer bushings - DIN42530 - Part A

DIN42530 - Part AFor bushingFig.1234HCrAd1d2d3d4d5h1h2Weight
typekVkVkVkVmmmmmmmmmmmmmmmmmmkg
DT1-250ADT1-250A11530507060250142732505045-0,15
DT1-630ADT1-630A11530508070630224347707055-0,40
DT1-1000ADT1-1000A115305085751000325365909055-0,60
DT1-2000ADT1-2000A11530508575200044668010410455-0,80
DT1-3150ADT1-3150A115305085753150508610012512555-1,30

Ceramic transformer bushings - DIN42530 - Part B

DIN42530 - Part BFor bushingFig.1234HCrAd1d2d3d4d5h1h2Weight
DT1-250BDT1-250B1153050306025030502660202080,10
DT1-630BDT1-630B1153050307063046704185282080,20
DT1-1000BDT1-1000B1153050357510005790461103725100,40
DT1-2000BDT1-2000B11530503575200070104641255125100,50
DT1-3150BDT1-3150B11530503575315090125801506125120,65
1 - Rated Highest voltage for equipment (Um)
2 - Rated Power Frequency Withstand Voltage, wet (50 Hz, 1 min)
3 - Rated Power Frequency Withstand Voltage, dry (50 Hz, 1 min)
4 - Rated Lightning impulse withstand, dry (1.2/50 μs)
Cr - Minimum creepage length
A - Rated Current