• Robert Dansertlaan 250, 1702 Groot-Bijgaarden, Belgium

Transformator bushings

Transformator bushings

Ceramic / porcelain material

Ceramic groupCeramic groupCeramic groupCeramic group
Sub-GroupC-110C-120C-130C-221
Silicious
Porcelain
Aluminous porcelain
Standard strength
Aluminous porcelain
High strength
Steatite low/loss
angle
PropertiesPropertiesPropertiesSymbolsUnitsAL2O3
<30%
AL2O3
30-50%
AL2O3
>50%
Apparent prosity (open)max.max.PaVolume %0.00.00.00.0
Bulk densitymin.min.δag/cm32,22,32,52,7
Flexural strengthmin.unglazedRfN/mm25090140140
min.glazedRfN/mm260110160-
Modulus of elasticityminEGPa6070100100
Mean coefficient linear expansionα 20-100°C10-6K-13-63-64-76-8
α 20-300°C10-6K-13-63-65-77-9
α 20-600°C10-6K-14-75-75-78-9
Specific heat capacity20°-100°CcpJ/kgK750÷900750÷900750÷900790÷920
Thermal conductivity20°-100°CλW/mK1÷2,51,2÷2,61,5÷4,02,3÷2,8
Resistance to thermal shockmin.ΔtK150150150100
Electric strengthmin.EdkV/mm20202020
Withstand voltagemin.UkV30303030
Relative permittivity48÷62 Hzεr6÷76÷76÷7,56
Dissipational 20°Cmax.48÷62 Hztanδ10-32525301,5
max.1 kHztanδ10-3----
max.1 MHztanδ10-31212151,2
Volume resistivity in terms of temperaturemin.20°CρvΩcm1013101310131012
min.200°CρvΩcm1081081081011
min.600°CρvΩcm104104104107
Temperature corresponding to a volume resistivitymin.100 MΩcmtK100°C200200200500
min.1 MΩcmtK1°C350350350800
For post insulators, hot-dip galvanized cast iron flanges assembled or with :
Sulphur cement = excellent mechanical performances and max use temperature 90°C - Reduced assembly time
Portland cement = max use temperature 200°C - Drying time in mould is longer

Ceramic transformator bushing 3 kV

Ceramic transformer bushings - DIN42539 - Part A

DIN42539 - Part AFor bushingFig.1234HCrAd1d2
e2
d3d4e1h1h2Weight
typekVkVkVkVmmmmmmmmmmmmmmmmmmkg
DT3-250ADT3-250A3284070135120250143732756085-0,40
DT3-630ADT3-630A3284070135120630224347907085-0,60
DT3-1000ADT3-1000A328407013512510003253651109085-1,00
DT3-2000ADT3-2000A3284070135125200044668012510585-1,40
DT3-3150ADT3-3150A32840701351253150508610014512585-2,00

Ceramic transformer bushings - DIN42539 - Part B

DIN42539 - Part BFor bushingFig.1234HCrAd1d2
e2
d3d4e1h1h2Weight
typekVkVkVkVmmmmmmmmmmmmmmmmmmkg
DT3-250BDT3-250B328407055120250406026702045100,30
DT3-630BDT3-630B328407055120630467041852845100,30
DT3-1000BDT3-1000B32840705512510005790461103745100,60
DT3-2000BDT3-2000B328407055125200070105641255145100,70
DT3-3150BDT3-3150B328407055125315090125801506145101,00
1 - Rated Highest voltage for equipment (Um)
2 - Rated Power Frequency Withstand Voltage, wet (50 Hz, 1 min)
3 - Rated Power Frequency Withstand Voltage, dry (50 Hz, 1 min)
4 - Rated Lightning impulse withstand, dry (1.2/50 μs)
Cr - Minimum creepage length
A - Rated Current