• Robert Dansertlaan 250, 1702 Groot-Bijgaarden, Belgium

Medium Voltage bushings

Traversée de jeux de barres intérieur/intérieur – Fiche catalogue
Download

Epoxy resin material

Raw materialAromatic epoxy resin, hardened with dicarboxylic acid anhydrides filled with silanised silica
Tensile strengthISO R 52779,28 N/mm²
Flexural strengthISO R 178102,45 N/mm²
Impact strengthISO 1799,2 kJ/m²
Noth impact strengthISO 1791,2 kJ/m²
Compressive StrengthISO R 604130 - 150 N/mm²
Critical stress intensity factor (K ic)CG 216-0/891.9 - 2.1 Mpa.m 1/2
Specific energy at break (Gic)CG 216-0/89300 - 340 J/m²
Glass transition pointISO 11357-1 (DSC)115 +5/-10 °C
Class of flammabilityUL 94V1 >12mm
Water absorbtionISO 620,018% by wt.
Coeff. of linear thermal expansionDIN 53752 (20 - 80°C)31-36*10-6 K-1
Tracking resistanceIEC 60112CTI >600 -0.0
Dielectric constantDIN 534834,2 (23 °C, 50 Hz)
Dissipation factorIEC 602500,0309 % (23°C - 50 Hz)
Dielectric strengthIEC 60243 - 117 - 20 kV/mm
HV arc resistanceASTM D 495182 - 189 seconds
DensityISO 1183-11.9 g/cm³
Colorbrown

GD bushings

Epoxy screwale medium voltage passing busbar bushings 6 to 36 kV

RefSAB23CrNDdfLcA
mmkVkVkVkVmmmmmmmmmmmmKg
B7402 -> 15612287512075001205595120501,1
B7072 -> 156122875120750014075115120501,3
B7082 -> 156122875120750016095135120501,6
B40542 -> 15612287512010000180115155120501,8
B40552 -> 15612287512010000210145185120502,2
B7412 -> 151224/3650125230125001405510215065,51,65
B7422 -> 151224/3650125230125001607512715070,51,96
B7092 -> 151224/36501252301250018095145150652,3
B40562 -> 151224/365012523012500200115165150652,6
B40572 -> 151224/365012523012500230145195150653,0
A - Rated Highest voltage for equipment (Um) - On metal panel
B - Rated Highest voltage for equipment (Um) - On insulating panel
2 - Rated Power Frequency Withstand Voltage, dry (50 Hz, 1 min)
3 - Rated Lightning impulse withstand (1.2/50 μs)
Cr - Creepage distance
N - Flexion resistance

RDIG 12 kV bushings

Epoxy medium voltage passing busbar bushings 12 kV indoor/indoor

REF.123CrNDdcfuabShZ
kVkVkVmmmmmmmmmmmmmmmmmmmmkg
2022326122875170750095551410014518512020552,18
201962412287517010000115751412016020013220552,51
202235512287517010000140951414518523016020553,91
2022357122875170100001601151416520525018020554,80
2022359122875170100001851451719023529020522,5556,30
20196721228751901000026019517270225280280285511,50
1 - Rated Highest voltage for equipment (Um)
2 - Rated Power Frequency Withstand Voltage, dry (50 Hz, 1 min)
3 - Rated Lightning impulse withstand (1.2/50 μs)
Cr - Creepage distance
N - Flexion resistance

RDIG 24/36 kV bushings

Epoxy medium voltage passing busbar bushings 24/36 kV indoor/indoor

REF.123CrNDdL1L2cfuabhZ
kVkVkVmmmmmmmmmmmmmmmmmmmmmmkg
20224112450125310750010558515240221201702151301456,84
20224162450125310750012580515240221401902351501457,46
202250024501253101250014598515240221602102551701459,13
20225072450125310125001651185152402818023028019014510,85
20225123670170380750011858645300281351702201402209,30
202258636701703807500140806453002816020024516522012,46
2022589367017038012500155986453002818022026518522013,78
20225953670170380125001751186453002820024028520522016,20
1 - Rated Highest voltage for equipment (Um)
2 - Rated Power Frequency Withstand Voltage, dry (50 Hz, 1 min)
3 - Rated Lightning impulse withstand (1.2/50 μs)
Cr - Creepage distance
N - Flexion resistance